CHENFENGIntelligent Control

Siemens 7MF0300-1QD01-5AF2SITRANS P320 gauge pressure transmitter, 16 bar

To be sourced Sourcing — lead time 7–10 days. Minimum order 1 piece, tested before packing.

No photo of this unit yet — ask for the serial's photo before you pay.

About this part

A gauge pressure transmitter with a 16 bar (232 psi) maximum span, 4–20 mA HART output, G½ A male process connection and a 316L diaphragm, in the dual-chamber die-cast aluminum housing with a local display.

On a P320 the order code carries the specification: the third block sets the measuring cell, the fourth the process connection, wetted material and approval set. Two transmitters that look identical can be a 1 bar and a 16 bar instrument, or differ in whether they carry FM and CSA. We decode the full string against the nameplate before quoting, because a range mismatch is the most common reason a replacement ends up back on the shelf.

Key specifications
SeriesSITRANS P320
TypeGauge pressure transmitter, dual chamber, with display
Measuring span0…16 bar (232 psi), adjustable
Output4–20 mA, HART 7
Accuracy0.065 % of span
Process connectionG½ A male, DIN EN 837-1, stainless steel 316L
Wetted parts316L diaphragm and measuring cell, silicone oil filling
HousingDie-cast aluminum, dual chamber, 2 × M20 × 1.5 cable entries
Degree of protectionIP66
TemperatureAmbient −40…85 °C, medium −40…100 °C
Ex approvalNone — non-hazardous area only
Net weight4 kg (per Siemens order data)
Country of originFrance — per Siemens order data, confirmed on the invoice

Specifications are decoded from the order code and checked against Siemens' published data. The suffix decides the range, the connection and the approvals — never order this family by the first two blocks alone.

Compatibility and replacement path

Models below share the slot, the loop or the engineering environment. Where the swap is not a drop-in, the reason is written next to it rather than left for commissioning day.

Compatible with

  • 7MF0300-1QD01-5AF1Same transmitter with the wider approval set (EAC, FM, CSA, KCC) and a closed display lid. Use it when the unit goes outside the EU or UK.
  • 7MF0300-1QE01-5AF2Alternate measuring cell variant in the same 16 bar class and the same housing. Confirm the cell code against the range configured in your DCS.
  • 7MF0300-1VE01-5AF2Same housing and electronics with the 160 bar cell. Only for taps where 16 bar is under-ranged; the connection and wiring are unchanged.

Supersedes — what this model replaced

  • SITRANS P DS III, 7MF4033 seriesThe gauge series the P320 replaced in service. Same two-wire 4–20 mA HART loop, but the terminal block and the HART menu differ, so the DCS device description may need updating.

Replaced by — what comes after it

None — the P320 is the current series and this order code is active. There is no announced successor.

Supply, testing and documents

How we verify this model before it ships

  1. Order code decoded first: the third block (1QD01) sets the cell and range, the fourth (5AF2) the connection, wetted material and approvals. Both are read from the nameplate and the label under the housing lid, then matched against Siemens order data.
  2. Loop test: 24 V supply, 4–20 mA driven at 4.0 / 8.0 / 12.0 / 16.0 / 20.0 mA through a reference meter, with the same points read back over HART.
  3. Mechanical: process thread inspected for galling, diaphragm photographed, housing seals and both M20 entries checked, display lid and glass inspected.
  4. Configuration: range, unit, damping and the 4 mA / 20 mA endpoints read out over HART and printed on the test sheet, so they can be compared with the DCS faceplate before installation.

Packing

Foam-lined carton with the process connection capped and the display lid taped. A mounting bracket or valve manifold, if ordered, is packed separately so it cannot mark the housing in transit.

Export documents

Commercial invoice, packing list with serial number, HS code 9026.20, five-point calibration certificate where available, certificate of origin on request.

Questions buyers ask about this model

Is this a new unit or a used pull?

The quote states which. New surplus comes in the original Siemens carton with the factory label and calibration certificate. A pull is cleaned, loop-tested against a reference gauge and shipped with our own test sheet and the same 12-month warranty.

Can you provide a calibration certificate?

For new units the factory five-point certificate travels with the instrument where the carton still has it. For pulls we issue our own five-point sheet naming the reference gauge used, which is what most auditors accept for a replacement instrument.

Can you ship DDP?

Yes, DDP to most destinations, or CIF / FOB Wuhan. Transmitters travel well by air; we quote both and show duty and VAT separately.

Why is the lead time 7–10 days?

This order code has to be sourced, not pulled from the shelf. We confirm the cell and approval codes with the supplier before committing, then give you the date the unit is tested and packed. If the range you need is urgent, the alternate cell variants we list may be on the shelf.

Do you supply the bracket, manifold and seals?

Yes. Mounting brackets, 3-valve and 5-valve manifolds and the matching sealing rings are quoted as separate lines so you can see what the installation actually costs.

Request a price for this part

Six fields, pre-filled with the model. You get unit price, condition, incoterm and the day it can leave Wuhan — within 4 working hours, Monday to Friday 09:00–18:00 CST.

7MF0300-1QD01-5AF2

Quoting several parts? Use the list form — it takes one number per line.

Part 7MF0300-1QD01-5AF2

A photo of the nameplate answers the suffix question faster than any description. Attach it to the reply or send it on WhatsApp.

Nothing is charged at this stage. Reply within 4 working hours, CST 09:00–18:00. Prefer email? [email protected].

Can’t find it? Send us the model number.

Most of what we ship is not listed here. Type the number from the nameplate and we check the shelf, the in-transit line and our supplier pool in one pass — including the previous-generation number it replaced and what has to change if it did.

A nameplate photo and the quantity is usually enough: email [email protected] or WhatsApp +86 182 0275 1913.