The ACS580 is ABB's general-purpose drive for pumps, fans and conveyors up to 500 kW; the ACS880 is the industrial range, up to 5.6 MW, with encoder feedback, a common DC bus and expandable safety functions.
The short answer
Buy the ACS580 for one motor on a normal-duty load in a 400 V panel. Buy the ACS880 when the load needs encoder feedback, regenerative braking, a shared DC bus, more than one option slot, or a frame above 500 kW.
- 150%overload for 60 s on a 580
- 690 Vtop voltage, ACS880 only
- 1option slot on a 580
When it fits, and when it does not
The two ranges share a control panel, a parameter structure and the Drive Composer tool, so a maintenance team that can commission one can commission the other. That is deliberate, and it is why the choice is often made on price alone, which is the wrong axis.
Three questions separate them in practice: how hard is the load pushed, does the motor need feedback, and does the braking energy have to go somewhere other than a resistor. Answer those and the model number follows.
| If the load looks like this | Specify | Because |
|---|---|---|
| Centrifugal pump or fan, 110% overload, 400 V supply | ACS580 | Normal-duty sizing plus built-in pump macros gets it running in an afternoon |
| Conveyor or mixer pulling 150% for a minute every cycle | ACS880, or a 580 sized on heavy-duty current | The 580 does it only when sized from the heavy-duty column, which erases most of the price gap |
| Winder, unwinder, crane or hoist | ACS880 | Torque at zero speed, brake control and encoder feedback are part of the platform |
| Machine where braking energy should feed another axis | ACS880 multidrive | Only the 880 has a common DC bus; the 580 is standalone with its own rectifier |
| Load above 500 kW, or a 690 V supply | ACS880 | Both limits sit outside the 580 range |
| Long motor cables, high switching frequency, hot cabinet | ACS880 with du/dt and common-mode filtering | An industrial-drive configuration, not a general-purpose one |
If two rows point at the ACS880, stop looking at the 580. If none do, the 580 is cheaper and the difference is real money.
Key differences
Read the overload, encoder and DC bus rows first. The rest are consequences: slot count, frame construction, enclosure and price all follow from those three.
| Item | ACS580 | ACS880 | Why it decides the order |
|---|---|---|---|
| Power range | 0.75 to 500 kW | 0.55 to 5600 kW | Above 500 kW there is no choice |
| Voltage | 200 to 240 V, 380 to 480 V | 200 to 240 V, 380 to 500 V, 525 to 690 V | A 690 V plant is ACS880 only |
| Overload | 150% for 60 s on heavy duty | 150% as standard, up to 200% peak | A 580 on a 150% duty must be sized from the heavy-duty column |
| Encoder feedback | None, and no interface option | TTL, HTL, resolver, EnDat, SSI through FEN modules | Closed-loop positioning rules the 580 out |
| Common DC bus | No | Yes, multidrive with shared DC bus | One axis absorbs the braking energy of another |
| Regenerative supply | No | Yes, with an active supply module | Cranes, test benches, downhill conveyors, unwinders |
| Safety | STO as standard (SIL 3, PL e) | STO plus FSO-12 and FSO-21 options | SS1, SLS and SBC inside the drive instead of relays |
| Option slots | One | Several: FIO, FEN, FPNO, FSO | On a 580 it is fieldbus or extra I/O, never both |
| Programming | Adaptive programming, 30 blocks | IEC 61131-3 with Drive Application Builder | Machine logic inside the drive needs the 880 |
| Enclosure | IP21 and IP55 | IP21, IP22, IP54, IP55, C5 coating | Wash-down and corrosive sites |
Deliberately absent: motor control quality. Both ranges come from ABB's common drive architecture and both hold torque at low speed on a standard induction motor.
What to specify, in order
Size on current and duty, never on kW
A 22 kW motor at 400 V draws roughly 42 A, but frames differ in what they deliver at 150% for 60 seconds. Take the nameplate current, multiply by the overload the process needs, then pick the frame from the matching column. A 580 sized on normal duty trips on a load its heavy-duty twin carries without complaint.
Decide whether the motor needs feedback
If the machine positions, synchronises two shafts or must hold torque at zero speed, the drive needs an encoder interface. The ACS580 has none and cannot be given one. That single question ends the discussion more often than price does.
Follow the braking energy
A hoist, a winder or a downhill conveyor regenerates. There are three destinations: a resistor as heat, a regenerative supply back to the network, or another axis on a common DC bus. The 580 offers the first only, so a project wanting the second or third is an 880 project.
Count the option slots before you commit
A 580 with PROFINET has already used its single slot. If the same drive also needs an extra analog input or a relay board, the slot count moves you to the 880. Check the option list at quote stage, not at commissioning.
Price the installed drive, not the drive
Filter, choke, brake chopper, resistor, encoder module, cabinet depth and cooling all sit around the unit. On a 250 kW pump those accessories can cost more than the difference between the ranges.
Common pitfalls
Sizing by kW on a 150% load
The most common re-order in this family. The kW on the nameplate describes normal duty; the frame you need is set by heavy-duty current. Send the motor current in the request, not only the power.
Expecting a brake chopper inside
On larger frames it is not, and the resistor is sized to the inertia and the deceleration time, not to the drive rating. A resistor picked by kW overheats on the first fast stop.
Treating IP55 as a trim option
The IP55 variant is a different frame with different depth and cable entry. An IP21 unit ordered into a wash-down area fails at the first hose-down, and water ingress is excluded from the warranty.
Copying a parameter file between ranges
Both use Drive Composer, so the backup looks portable. It is not: parameter groups and default macros differ, and a 580 backup restored into an 880 leaves part of the configuration at factory values.
Questions we get on the quote desk
Can an ACS580 replace an ACS880 if the kW matches?
Which drive for a pump station with three pumps?
Is a soft starter enough instead of a drive?
Can either range run on 690 V?
The models this guide names
Where these models sit in the catalog
-
ACS580-01-05A7-4
In the catalog
ABB
ACS580, 5.7 A, 400 V, IP21. The small pump and fan frame we keep in stock.
Open the part -
ACS580-01-026A-4
Quote on request
ACS580, 26 A, 400 V. The workhorse frame for an 11 to 15 kW pump or fan.
Request a price -
ACS880-01-09A4-4
Quote on request
ACS880, 9.4 A, 400 V. Entry frame of the industrial range, STO included.
Request a price -
ACS880-01-145A-3
Quote on request
ACS880, 145 A, 400 V. Heavy-duty loads in the 75 kW class.
Request a price -
PSTX170-600-70
Quote on request
PSTX soft starter, 170 A. For the pump that needs a controlled start, not variable speed.
Request a price