CHENFENGIntelligent Control

Replacement & obsolescence 2026-11-03 6 min read

Replacing an ACS355: ACS380, ACS580, or one more tested spare

ABB ended ACS355 sales in 2025. Which route is right depends on whether the machine uses the drive's own sequence logic or only needs to turn a motor.

Definition

The ACS355 machinery drive, 0.37 to 22 kW, left new-part sales in 2025; the ACS380 is ABB's direct successor, and the ACS580 is the route for machines that only need general-purpose speed control.

The short answer

Convert to an ACS380 when the machine uses the drive's built-in sequence programming or an F-series fieldbus adapter. Convert to an ACS580 when it is a fan, pump or simple conveyor with no logic inside the drive. Keep tested ACS355 units for machines due to be retired.

  • 0.37-22 kWthe ACS355 range
  • 3routes after end of sale
  • 33-36STO terminals that move
01

When it fits, and when it does not

An ACS355 that fails at two in the morning is not a selection problem, it is a stock problem. For a machine with two years left, the honest answer is a tested spare, not a conversion project: the conversion costs more and adds commissioning risk to a line that is leaving.

For everything else, ask what the old drive did that a general-purpose drive cannot. Usually one of three things: sequence programming living inside the drive, an F-series fieldbus adapter with no equivalent slot on the new platform, or a cabinet with no spare depth for a taller frame.

Choosing the route by what the machine actually needs
If the machineRouteWhy
Is due to be retired within two yearsTested ACS355 spareConversion cost and commissioning risk buy nothing on a line that is leaving
Runs its cycle with sequence programming in group 84ACS380Adaptive programming keeps the logic inside the drive instead of adding a small PLC
Talks PROFINET through a FENA adapterACS380 with the matching BCON variantF-series adapters do not carry over; the fieldbus becomes part of the drive order
Is a pump, fan or simple conveyor with no internal logicACS580More I/O and a wider power range at a lower cost per kW
Needs closed-loop control or positioningACS880Encoder interfaces on a motion-capable platform; neither the 380 nor the 580 has one
Runs 22 kW at 150% overloadSize on heavy-duty current, not on kWACS355 ratings are heavy duty by default; the new tables are not

Two routes end in a part we stock and one ends in an order placed with ABB. All three are legitimate; the expensive mistake is choosing on kW alone.

02

Key differences

ACS355 and ACS380 share the machinery intent, the DIN-rail mounting and ABB's common parameter naming. They do not share a terminal strip, an option slot or a parameter file, and the frame is taller. This is what to check before the old drive comes off the wall.

ACS355 against its two replacement routes
ItemACS355 (existing)ACS380 (successor)ACS580 (general purpose)
Power range0.37 to 22 kW0.25 to 22 kW0.75 to 500 kW
Drive classMachinery driveMachinery driveGeneral purpose
Datasheet default ratingHeavy dutyNormal duty column firstNormal and heavy duty columns
Standard I/O5 DI, 1 AI, 1 AO, 1 relay4 DI, 2 AI, 1 AO, 1 DO, 1 relay6 DI, 2 AI, 2 AO, 3 relay
STO terminals33, 34, 35, 36S1, S2, SGNDSeparate STO terminal block
FieldbusF-series adapters: FENA, FPBA, FMBABCON, BIO and BAPO modulesFPNO or FPBA in the single slot
ProgrammingSequence programming, group 84Adaptive programmingAdaptive programming
Frame R1 heightAbout 169 mmAbout 223 mmTaller again
Best forMachines with internal logicMachines with internal logicPumps, fans, conveyors

Frame dimensions change with the fieldbus module fitted and vary by variant. Measure the cabinet before ordering, not after the drive lands on the bench.

03

What to specify, in order

Read the rating column the old drive was sold under

ACS355 datasheets list heavy-duty current as the default figure; ACS380 and ACS580 lead with normal duty. Take the motor nameplate current, apply the overload the machine needs, then choose the frame from the heavy-duty column. A same-kW swap can land thirty percent short on current.

Map the terminals on paper before the drive arrives

STO moves from terminals 33 to 36 to S1, S2 and SGND. DI5 disappears, the relay output changes number, and the digital inputs are assigned differently by default. Draw the new strip, mark the wires, then terminate once.

Port the logic deliberately, not from memory

Sequence programming in group 84 has no line-by-line equivalent; the new drives use adaptive programming blocks. If the old program had more than a dozen steps, budget a day with Drive Composer and a test motor rather than finding the gaps on the machine.

Check the cabinet depth and the door

The R1 frame grows from roughly 169 mm to 223 mm in height and the depth changes with it. In a shallow cabinet the drive fits the DIN rail and not the closed door, which is a panel modification discovered at installation.

Keep one tested ACS355 per critical machine

For a line that is not converting this year, a tested spare is the cheapest risk control available: it removes a four-week sourcing exercise from a breakdown. We test and record each unit before it ships and state condition on the quote.

04

Common pitfalls

  • Matching kW instead of current

    A 2.2 kW ACS355 is a heavy-duty 5.6 A device. The ACS380 frame that matches it in the heavy-duty column is not the frame that matches it on the normal-duty kW line, and the gap runs to thirty percent.

  • Asymmetric STO wiring leaves the drive dead

    On the ACS380 both safe inputs have to be wired and bridged correctly. A single-channel bridge produces a permanent STO active fault that reads like a failed drive and is really a terminal mistake.

  • DriveWindow files cannot be opened by the new tool

    .dwg and .dp5 backups are not readable by Drive Composer. Parameters have to be transcribed group by group from a printout, which is why the old backup should be printed before the drive is removed.

  • Option modules do not migrate

    Encoder, fieldbus and I/O modules from the F-series are physically incompatible with the new slots. Every module in the old drive has to be re-specified, and each one adds lead time.

  • IP66 is a different drive, not a seal

    The IP66 variant has different dimensions and cable entries. An IP20 unit with a cover is not IP66, and water ingress is excluded from the warranty for exactly this reason.

05

Questions we get on the quote desk

Can I still buy a new ACS355?
Not from ABB as a new part; the range left new-part sales in 2025. What remains is distributor stock and tested second-source units. Every quote states the condition: new surplus, refurbished or used-tested.
Is an ACS580 a valid replacement for an ACS355?
For a fan, pump or simple conveyor, yes. It brings more I/O, a wider power range and a general-purpose enclosure, but it is physically larger and the frame does not match the machinery-class footprint. If the logic lives in the drive, the ACS380 is closer.
Do I have to change the motor cable?
Usually not, but check the EMC filter arrangement and the permitted cable length for the new frame. A drive with a smaller internal filter can need an external one on a long unshielded run, which is a cabinet change.
What replaces an ACSM1 motion drive?
Not the ACS380 or ACS580; those are speed-control drives. The route is an ACS880-01 with the motion control program and the right encoder interface, which is a larger project and should be quoted as one.
06

The models this guide names

Still deciding

Send the model number. We answer with a price, a condition and a date.

One line per part is enough. Quote back within 4 working hours, Monday to Friday 09:00–18:00 CST. No account, no minimum quantity, no obligation.

WhatsApp Request a Quote
WhatsApp