Replacing an S7-300 with an S7-1500: the mapping table and the order it has to happen in

New-part sales for the S7-300 and ET 200M ended on 1 October 2025. Spare-part supply runs to 2033, which is the whole planning horizon you get.

Definition

S7-300 CPUs and ET 200M modules left new-part sales on 1 October 2025; Siemens plans spare-part supply until October 2033, and the functional successor is the S7-1500 with ET 200MP or ET 200SP I/O.

The short answer

If the plant has seven years left, buy tested spares of the critical modules now and migrate one line per shutdown. If it has three years left, buy the spares and do not start a migration you will not finish.

  • 1 Oct 2025new-part sales ended
  • Oct 2033planned spare-part end
  • 0 of 8S7-300 modules that drop straight in
01

When it fits, and when it does not

The S7-300 did not break. It reached the end of its product life, which is a different problem: the plant still runs, the spare-part window still has years in it, and the successor is not a drop-in. Everything after that is a decision about time and production windows.

This is the rack we are asked about most often: a 315-2DP with a handful of SM 321, 322, 331 and 332 cards, an IM 153 and the rail. The last column of the table is where a migration actually spends its hours, and it never appears in a catalog.

Migrate, or hold spares, decided by remaining plant life
If the plant will runDo thisWhy
Under three more yearsBuy tested spares of the exact modules and migrate nothingA migration that outlives the plant is engineering spent for no return
Three to seven yearsSecure spares for the critical modules, migrate one line per shutdownSpreads the cost, keeps production, leaves the old lines supported to the end
More than seven yearsMigrate, and stop buying S7-300 spares except for lines still waitingSpare-part supply is planned to end in October 2033, inside that horizon
Line with a dozen PROFIBUS slaves1516-3 PN/DP, or 1513-1 PN plus CM 1542-5Keeping DP is cheaper than converting twelve slaves in one shutdown

Siemens lifecycle notices: phase-out announced 1 October 2023, type discontinuation 1 October 2025, planned discontinuation 1 October 2033. Individual accessories can leave earlier, so check the order number itself.

02

The 315 rack, mapped part by part

Read this as a bill of materials plus a work list. The left two columns are what is in the panel today, the middle two are what replaces it, and the right column is what the electrician and the programmer do that the catalog does not mention.

S7-300 to S7-1500 order-number mapping
S7-300 item and order numberS7-1500 equivalent and order numberWhat changes
CPU 315-2DP
6ES7315-2AH14-0AB0
CPU 1513-1 PN, or 1513F-1 PN if fail-safe
6ES7513-1AL02-0AB0
No DP port: add CM 1542-5 or convert the slaves
CPU 317-2DP
6ES7317-2AK14-0AB0
CPU 1516-3 PN/DP
6ES7516-3AN02-0AB0
The lowest 1500 CPU with an integrated DP port
SM 321, DI 16x24VDC
6ES7321-1BH02-0AA0
DI 16x24VDC HF
6ES7521-1BH00-0AB0
Front connector ordered separately; diagnostics per channel
SM 322, DO 16x24VDC/0.5A
6ES7322-1BH01-0AA0
DQ 16x24VDC/0.5A HF
6ES7522-1BH01-0AB0
Same 0.5 A rating; re-check lamp and valve loads
SM 331, AI 8x12bit
6ES7331-7KF02-0AB0
AI 8xU/I/RTD/TC ST
6ES7531-7KF00-0AB0
16-bit instead of 12-bit: the scaling must be redone
SM 332, AO 4x12bit
6ES7332-5HD01-0AB0
AQ 4xU/I ST
6ES7532-5HD00-0AB0
Range set in configuration, not by wire jumpers
SM 323, DI 8 / DO 8
6ES7323-1BH01-0AA0
DI 8x24VDC BA plus DQ 8x24VDC BA
6ES7521-1BF00-0AB0 and 6ES7522-1BF00-0AB0
No combined card: two modules replace one, the rack grows
IM 153-2, ET 200M
6ES7153-2BA10-0XB0
IM 155-6 PN HF, ET 200SP
6ES7155-6AU01-0BN0
The interface is the easy half: no ET 200M card runs behind it
PS 307, 5 A
6ES7307-1EA01-0AA0
PM 1507, 24 V DC / 8 ARecalculate the 24 V budget; a full 1500 rack draws more
Rail, 480 mm
6ES7390-1AE80-0AA0
Rail, 482.6 mm
6ES7590-1AB60-0AA0
Different length and drill pattern: the old holes do not line up
Micro Memory Card
6ES7953-8Lx00-0AA0
SIMATIC memory card
6ES7954-8Lx03-0AA0
The MMC does not fit, and the CPU will not start without the new card

Order numbers as published by Siemens; confirm lifecycle status in SiePortal before a project order. Where two numbers are given, the first is the standard variant and the second the fail-safe one.

03

What to specify, in order

Freeze the program before anyone touches the hardware

Archive the S7-300 project with firmware and comments, print the symbol table, export the data blocks. TIA Portal needs the original project to migrate; a memory card with an uncommented program turns a two-day conversion into a rewrite from the electrical drawings.

Decide PROFIBUS or PROFINET before choosing the CPU

If the segment carries a dozen slaves, keeping DP is cheaper than converting them: a 1516-3 PN/DP with its integrated port, or a 1513-1 PN with CM 1542-5. Converting slaves is a separate project with its own shutdown.

Re-scale the analog channels instead of copying the block

The 331 delivers 12-bit raw values, the 531 delivers 16-bit. A copied scaling block produces a reading that looks plausible and drifts at the top of the range, which is exactly where the alarm sits. Re-do NORM_X and SCALE_X per channel against a simulator.

Order rail, connectors and card as one kit

The 482.6 mm rail has a different drill pattern, the front connectors are never in the box, and the CPU will not run without a SIMATIC memory card. A kit that arrives without them sits on the floor while the shutdown window closes.

Migrate rack by rack, and prove each one before the next

One line per shutdown, old and new racks on the same PROFINET backbone where the process allows it. A plant-wide cutover concentrates every unknown into one weekend, and the unknowns in a 15-year-old panel are not in the migration guide.

04

Common pitfalls

  • The MMC does not fit, and its absence stops the CPU

    S7-1500 CPUs run from a SIMATIC memory card in a different slot. Order it with the CPU: a 1513 without one is a doorstop, and the S7-300 card cannot be reused.

  • A 1513 has no PROFIBUS port

    The 315-2DP had one, and the program probably uses it for more than programming. On a 1513 the DP segment needs CM 1542-5 or moves to PROFINET. Both are real work, neither is in the price of the CPU.

  • 12-bit to 16-bit silently breaks analog scaling

    The raw range changes by a factor of sixteen. A copied FC105 call climbs to full scale at the wrong point, and the first symptom is usually a nuisance trip on an over-range alarm.

  • Combined DI/DO cards have no single successor

    An SM 323 becomes two modules, so the rack grows a slot and the panel grows 25 to 35 mm. On a crowded door that is a layout change, discovered at installation.

  • Direct peripheral access fails on optimized blocks

    S7-300 code often reads PIB or writes PQB. S7-1500 blocks are optimized by default and refuse absolute access, so symbolic access has to be chosen deliberately, block by block.

05

Questions we get on the quote desk

Can I still buy new S7-300 modules?
Not through normal sales since 1 October 2025. What remains is distributor stock, Siemens spare-part service and tested second-source units. We state condition on every line: new surplus, refurbished or used-tested.
Is a 1513F the right replacement for a 315-2DP?
Only if the rack has fail-safe I/O. The F CPU carries safety overhead in price and program structure. For a standard rack the mapping is the 1513-1 PN, and the F variant is certification nobody asked for.
How long does the migration take?
For a medium program, three to ten working days of engineering for conversion and I/O test, plus one shutdown window for installation and commissioning. Engineering is the variable, not the hardware.