S7-300 CPUs and ET 200M modules left new-part sales on 1 October 2025; Siemens plans spare-part supply until October 2033, and the functional successor is the S7-1500 with ET 200MP or ET 200SP I/O.
The short answer
If the plant has seven years left, buy tested spares of the critical modules now and migrate one line per shutdown. If it has three years left, buy the spares and do not start a migration you will not finish.
- 1 Oct 2025new-part sales ended
- Oct 2033planned spare-part end
- 0 of 8S7-300 modules that drop straight in
When it fits, and when it does not
The S7-300 did not break. It reached the end of its product life, which is a different problem: the plant still runs, the spare-part window still has years in it, and the successor is not a drop-in. Everything after that is a decision about time and production windows.
This is the rack we are asked about most often: a 315-2DP with a handful of SM 321, 322, 331 and 332 cards, an IM 153 and the rail. The last column of the table is where a migration actually spends its hours, and it never appears in a catalog.
| If the plant will run | Do this | Why |
|---|---|---|
| Under three more years | Buy tested spares of the exact modules and migrate nothing | A migration that outlives the plant is engineering spent for no return |
| Three to seven years | Secure spares for the critical modules, migrate one line per shutdown | Spreads the cost, keeps production, leaves the old lines supported to the end |
| More than seven years | Migrate, and stop buying S7-300 spares except for lines still waiting | Spare-part supply is planned to end in October 2033, inside that horizon |
| Line with a dozen PROFIBUS slaves | 1516-3 PN/DP, or 1513-1 PN plus CM 1542-5 | Keeping DP is cheaper than converting twelve slaves in one shutdown |
Siemens lifecycle notices: phase-out announced 1 October 2023, type discontinuation 1 October 2025, planned discontinuation 1 October 2033. Individual accessories can leave earlier, so check the order number itself.
The 315 rack, mapped part by part
Read this as a bill of materials plus a work list. The left two columns are what is in the panel today, the middle two are what replaces it, and the right column is what the electrician and the programmer do that the catalog does not mention.
| S7-300 item and order number | S7-1500 equivalent and order number | What changes |
|---|---|---|
CPU 315-2DP6ES7315-2AH14-0AB0 | CPU 1513-1 PN, or 1513F-1 PN if fail-safe6ES7513-1AL02-0AB0 | No DP port: add CM 1542-5 or convert the slaves |
CPU 317-2DP6ES7317-2AK14-0AB0 | CPU 1516-3 PN/DP6ES7516-3AN02-0AB0 | The lowest 1500 CPU with an integrated DP port |
SM 321, DI 16x24VDC6ES7321-1BH02-0AA0 | DI 16x24VDC HF6ES7521-1BH00-0AB0 | Front connector ordered separately; diagnostics per channel |
SM 322, DO 16x24VDC/0.5A6ES7322-1BH01-0AA0 | DQ 16x24VDC/0.5A HF6ES7522-1BH01-0AB0 | Same 0.5 A rating; re-check lamp and valve loads |
SM 331, AI 8x12bit6ES7331-7KF02-0AB0 | AI 8xU/I/RTD/TC ST6ES7531-7KF00-0AB0 | 16-bit instead of 12-bit: the scaling must be redone |
SM 332, AO 4x12bit6ES7332-5HD01-0AB0 | AQ 4xU/I ST6ES7532-5HD00-0AB0 | Range set in configuration, not by wire jumpers |
SM 323, DI 8 / DO 86ES7323-1BH01-0AA0 | DI 8x24VDC BA plus DQ 8x24VDC BA6ES7521-1BF00-0AB0 and 6ES7522-1BF00-0AB0 | No combined card: two modules replace one, the rack grows |
IM 153-2, ET 200M6ES7153-2BA10-0XB0 | IM 155-6 PN HF, ET 200SP6ES7155-6AU01-0BN0 | The interface is the easy half: no ET 200M card runs behind it |
PS 307, 5 A6ES7307-1EA01-0AA0 | PM 1507, 24 V DC / 8 A | Recalculate the 24 V budget; a full 1500 rack draws more |
Rail, 480 mm6ES7390-1AE80-0AA0 | Rail, 482.6 mm6ES7590-1AB60-0AA0 | Different length and drill pattern: the old holes do not line up |
Micro Memory Card6ES7953-8Lx00-0AA0 | SIMATIC memory card6ES7954-8Lx03-0AA0 | The MMC does not fit, and the CPU will not start without the new card |
Order numbers as published by Siemens; confirm lifecycle status in SiePortal before a project order. Where two numbers are given, the first is the standard variant and the second the fail-safe one.
What to specify, in order
Freeze the program before anyone touches the hardware
Archive the S7-300 project with firmware and comments, print the symbol table, export the data blocks. TIA Portal needs the original project to migrate; a memory card with an uncommented program turns a two-day conversion into a rewrite from the electrical drawings.
Decide PROFIBUS or PROFINET before choosing the CPU
If the segment carries a dozen slaves, keeping DP is cheaper than converting them: a 1516-3 PN/DP with its integrated port, or a 1513-1 PN with CM 1542-5. Converting slaves is a separate project with its own shutdown.
Re-scale the analog channels instead of copying the block
The 331 delivers 12-bit raw values, the 531 delivers 16-bit. A copied scaling block produces a reading that looks plausible and drifts at the top of the range, which is exactly where the alarm sits. Re-do NORM_X and SCALE_X per channel against a simulator.
Order rail, connectors and card as one kit
The 482.6 mm rail has a different drill pattern, the front connectors are never in the box, and the CPU will not run without a SIMATIC memory card. A kit that arrives without them sits on the floor while the shutdown window closes.
Migrate rack by rack, and prove each one before the next
One line per shutdown, old and new racks on the same PROFINET backbone where the process allows it. A plant-wide cutover concentrates every unknown into one weekend, and the unknowns in a 15-year-old panel are not in the migration guide.
Common pitfalls
The MMC does not fit, and its absence stops the CPU
S7-1500 CPUs run from a SIMATIC memory card in a different slot. Order it with the CPU: a 1513 without one is a doorstop, and the S7-300 card cannot be reused.
A 1513 has no PROFIBUS port
The 315-2DP had one, and the program probably uses it for more than programming. On a 1513 the DP segment needs CM 1542-5 or moves to PROFINET. Both are real work, neither is in the price of the CPU.
12-bit to 16-bit silently breaks analog scaling
The raw range changes by a factor of sixteen. A copied FC105 call climbs to full scale at the wrong point, and the first symptom is usually a nuisance trip on an over-range alarm.
Combined DI/DO cards have no single successor
An SM 323 becomes two modules, so the rack grows a slot and the panel grows 25 to 35 mm. On a crowded door that is a layout change, discovered at installation.
Direct peripheral access fails on optimized blocks
S7-300 code often reads PIB or writes PQB. S7-1500 blocks are optimized by default and refuse absolute access, so symbolic access has to be chosen deliberately, block by block.
Questions we get on the quote desk
Can I still buy new S7-300 modules?
Is a 1513F the right replacement for a 315-2DP?
How long does the migration take?
The models this guide names
Where these models sit in the catalog
-
6ES7315-2AH14-0AB0
Quote on request
CPU 315-2DP, the module this guide replaces, still stocked tested for lines not migrating yet.
Request a price -
6ES7331-7KF02-0AB0
Quote on request
SM 331, AI 8x12bit. The analog card in most 300 racks, and the one whose scaling breaks first.
Request a price -
6ES7513-1FL02-0AB0
In the catalog
Siemens
CPU 1513F-1 PN. 450 KB code, 1.5 MB data, integrated fail-safe control.
Open the part -
6ES7590-1AB60-0AA0
Quote on request
Mounting rail, 482.6 mm. Order it with the first module, not after the panel is drilled.
Request a price -
6ES7155-6AU01-0BN0
Quote on request
IM 155-6 PN HF for ET 200SP, the replacement for an IM 153 station.
Request a price